Building 1362 Dry Cooler Replacement
Agency: | DEPT OF DEFENSE |
---|---|
Level of Government: | Federal |
Category: |
|
Opps ID: | NBD00159034117102640 |
Posted Date: | Aug 8, 2023 |
Due Date: | |
Solicitation No: | N4008523D0039 |
Source: | https://sam.gov/opp/d4155d4b6f... |
- Contract Award Date: Apr 01, 2023
- Contract Award Number: N4008523D0039
- Task/Delivery Order Number: N4008523F5023
- Contractor Awarded Unique Entity ID: Y9FRK3A8ZNE7
- Contractor Awarded Name: Aaecon General Contracting LLC
- Contractor Awarded Address: Louisville , KY 40204 USA
- Base and All Options Value (Total Contract Value): $192,821.02
- Contract Opportunity Type: Award Notice (Original)
- All Dates/Times are: (UTC-04:00) EASTERN STANDARD TIME, NEW YORK, USA
- Original Published Date: Aug 08, 2023 10:50 am EDT
- Inactive Policy: Manual
- Original Inactive Date: Aug 31, 2023
-
Initiative:
- None
- Original Set Aside: 8(a) Sole Source (FAR 19.8)
- Product Service Code: J041 - MAINT/REPAIR/REBUILD OF EQUIPMENT- REFRIGERATION, AIR CONDITIONING, AND AIR CIRCULATING EQUIPMENT
-
NAICS Code:
- 238190 - Other Foundation, Structure, and Building Exterior Contractors
-
Place of Performance:
Newport , RI 02841USA
This project consist of removing and replacing existing rooftop dry cooler (DC-1) at
Building 1362. Existing dry cooler is a Liebert Dry Cooler Model DDNT880AS5910.
Dry Cooler. The dry cooler shall be factory fabricated and shall comprise of casing,
coil, and fan sections. The casing shall be constructed of aluminum sheets with
aluminum legs, casing and legs provided with manufacturer's standard corrosion
resistant finish. The cooling fluid (water/glycol solution) shall flow through a coil
made up of copper tubes and aluminum fins. The coils shall be leak tested at factory
at 300 psi. The fan section of the dry cooler shall comprise of factory balanced,
direct driven metal propeller fan(s) complete with slow speed motor(s) and fan
guard(s). The fan(s) shall be arranged for vertical discharge. The electrical
connections and control connections shall be provided in a weatherproof enclosure
mounted integral with the dry cooler. Provide manufacturers corrosion protection for
the dry cooler coils due to proximity to the coastal installation. Include option for
extended leg support extensions to maximzie air flow.